| ITEM / MODEL | MSP-25L | MSP-25R | |
| Input Signal | 0.14~0.7MPa(20~105psi) | ||
| Supply Pressure | 0.14~0.7MPa(20~105psi) | ||
| Stroke | 10~150mm(standard); 5~130mm(adaptor) | 0°to 90 | |
| Impedance | Max.500Ω / 20mADC | ||
| Air Connection | PT(NPT)1/4 | ||
| Gauge Connection | PT(NPT)1/8 | ||
| Conduit | PF1/2 (G1/2) | ||
| Repeatability | ±0.5% F.S. | ||
| Ambient temp. | Normal: | -20 to 85℃ | |
| Low temp.: | -40 to 80℃ | ||
| Linearity | ±0.5% F.S. | ||
| Hysteresis | ±0.5% F.S. | ||
| Sensitivity | ±0.5% F.S. | ||
| Air Consumption | Stable condition:<0.0006Nm 3/h | ||
| Flow Capacity | 70LPM (SUP=0.14MPa) | ||
| Output Characteristics | Linear (default); Quick open; Equal percentage ; User defined | ||
| Material | Aluminum or SS316L | ||
| Enclosure | IP66 | ||
| Explosion Proof | Ex ia IIC T6 Ga; Ex ia IIIC T135℃ Db | ||

Another feature that distinguishes the piezoelectric valve principle is its high vibration resistance. The overall module structure of the positioner has few moving parts, no mechanical force balance mechanism, and good anti-seismic performance. This feature is especially important in applications where vibration can cause disturbances in the system. Fast response times and long service life are other benefits of the piezoelectric valve principle. Response times as low as 2 milliseconds make the positioner highly responsive to changes in system parameters. In addition, the operation life of the piezoelectric module is at least 500 million times, ensuring reliable and long-lasting performance. With its advanced features and advantages, the intelligent positioner is the main device for controlling the opening of the valve in the pneumatic system. It can accurately adjust any opening of the valve, and is an essential tool for adjusting the flow of air or gas. This smart positioner offers unrivaled performance, reliability and economy, making it the first choice for a wide variety of industrial applications. In conclusion, combined with the product features and description, the smart positioner using the piezoelectric valve principle is the best choice to meet your valve control needs. Low operating costs, strong vibration resistance, fast response time and long service life are all key features that set this product apart. If you're looking for a smart locator with unrivaled performance, you've just found it. Choose our smart positioners based on the piezoelectric valve principle today and experience effortless valve control.The P13 piezoelectric valve electrical control module imported from Germany HOERBIGER is selected. Compared with the traditional nozzle-baffle principle positioner, it has the advantages of low air consumption, low power consumption, fast response and long life.
Install MSP-25L with mounting bracket 1. Make a mounting bracket for the positioner that can be properly connected to the actuator bracket. Note: it is required that the rotation angle of the lever within the stroke of the valve is adjustable within the permissible angle range when making the bracket. 2. Using fixed bolts to connect the mounting bracket and MSP-25L, installation diagram is shown below. The standard bolt specification for fixing the positioner is M8* 1.25P. 3. After fixed the bracket and positioner, do not tighten the bolts completely before connecting to the actuator, and leave a certain gap for later adjustment. 4. Install the connecting rod on the feedback lever of MSP-25L when connecting valve stem and actuator push rod. The height of the groove on the feedback lever of MSP-25L is 6.5mm, so the diameter size of the connecting rod should be less than 6.3mm. 5. Insert the connecting rod mounted on the stem connector into the groove of the feedback lever.As shown above, the connectior rod should be inserted into the fixed spring on the feedback lever to reduce the lag. 6. The actuator is separately connected with the air source tube, and the pressure is adjusted through the air filter regulator to open the valve to 50% position, and the position of the positioner is adjusted up and down to make the feedback lever in the horizontal state (the feedback lever is vertical to the valve stem), and then tighten the fixation bolts.